Kirloskar 750 kVA - 1010 kVA

Prime Rating at rated rpm (as per ISO8528 ) 1 kVA 750 HD 900 HD 1010 HD
kW 600 720 808
Genset Model KG1-750WS KG1-900WS KG1-1010WS
Frequency Hz 50 50 50
Power factor lagging 0.8 0.8 0.8
Voltage (with Three Phase Supply ) V 415 3Ø 415 3Ø 415 3Ø
Governing class (As per ISO 8528 Part-V) G3 G3 G3
Noise level dBA < 75 < 75 NA
Fuel Consumption* At 100 % Load Ltrs/hr 154 197 199
At 75 % Load 126.4 163 155
At 50 % Load 89.7 120 112
Fuel tank capacity Ltrs 990 990 990
Weight of genset with Dry Kg 8300 13600 13200
canopy (approx.)^
Overall dimensions Length mm 6800 8000 7800
of genset Width mm 2300 2300 2300
Height mm 2713 2713 2713
Electrical Battery starting voltage Volts-DC 24 24 24
ENGINE
Engine Model DV12ETA G11 DV16ETA G2 DV16ETA G1
Rated output (Prime Continuous rating as kW 663 799 889
per ISO 3046) HP 901 1086 1210
No. of cylinder Number 12 16 16
Cubic capacity 2 Ltrs 23.88 31.86 31.86
Bore x Stroke mm 130 x 150 130 x 150 130 x 150
Rated Speed RPM 1500 1500 1500
Aspiration NA/TC/TA TA TA TA
Lube Oil change period hrs 500 500 500
Lube Oil Sump Capacity Ltrs 53 130 130
Coolant Capacity with Radiator Ltrs 145 205 205
ALTERNATOR
Insulation Class
Ingression Protection
Alternator Efficiency (at 100% load) 0.8 pf** 94.6 95.3 95.1
Alternator Efficiency (at 75% load) 0.8 pf** 94.9 95.5 95.4
Permissible Voltage Dip at Full Load 0.8 pf Lag < 20 % < 20 % < 20 %
Time Permitted to build up rated voltage at rated RPM
Short Circuit Withstand Time sec
Overload Withstand Capacity %

For intermediate ratings, kindly contact nearest KOEL office

Notes
^ Tolerances Apply
*With 0.845 Specific Gravity of diesel ( 5 % Tolerance )

** Efficiency of Alternator as per standards IS 4722 and IEC 34-1
** For Site Conditions other than standard operating conditions consult KOEL for available prime power.

<< Back to Product List