Kirloskar diesel genset liquid cooled
160 kVA - 250 kVA

Prime Rating at rated rpm ( as per ISO8528)1

kVA

160

180

200

250

kW

128

144

160

200

Genset Model

KG1-160WS

KG1-180WS

KG1-200WS

KG1-250WS

Frequency

Hz

50

50

50

50

Power factor

lagging

0.8

0.8

0.8

0.8

Voltage

V

415 3Ø

415 3Ø

415 3Ø

415 3Ø

Governing class (As per ISO 8528 Part-V)

 

G3

G3

G3

G3

Noise level

dBA

< 75

< 75

< 75

< 75

Fuel Consumption*  

At 100 % Load

Ltrs/hr

36.6

41.3

45.9

56.9

At 75 % Load

27.7

30.9

34.4

42.6

At 50 % Load

19.1

22.7

25.2

29.9

Fuel tank capacity

Ltrs

300

460

460

460

Dry weight of genset with canopy (approx..)^

Kg

2700

3900

3900

4100

Wet weight of genset with canopy (approx..)^

Kg

2950

4300

4300

4500

Overall dimensions of genset (L x W x H)^

mm

4040 x
1540 x
1916

4340 x
1740 x
1970

4340 x
1740 x
1970

4340 x
1740 x
1975

Height including Silencer

mm

2385

2609

2609

2615

Electrical Battery starting voltage 

Volts-DC

12

24

24

24

ENGINE

Engine Model

 

6K1080TA G2

6SL1500TA G2

6SL1500TA G2

6SL1500TA G3

Rated output (Prime Continuous rating as per ISO 8528-1)

kW

147

183

183

228

HP

200

248

248

310

No. of cylinder

Number

6

6

6

6

Cubic capacity 2

Ltrs

6.48

8.86

8.86

8.86

Bore x Stroke

mm

105 x 125

118 x 135

118 x 135

118 x 135

Rated Speed

RPM

1500

1500

1500

1500

Aspiration

NA/TC/TA

TA

TA

TA

TA

Lube Oil change period

hrs.

500

500

500

500

Lube Oil Sump Capacity

Ltrs

18.0

27.0

27.0

27.0

Coolant Capacity

Ltrs

28.0

32.0

32.0

32.0

ALTERNATOR

Insulation Class

 

Class H

Ingression Protection

 

IP 23

Alternator Efficiency (at 100% load) 0.8 pf**

 

93.0

93.0

93.5

93.6

Alternator Efficiency (at   75% load) 0.8 pf**

 

93.3

93.6

93.8

93.9

Permissible Voltage Dip at Full Load 0.8 pf Lag

 

< 20 %

 < 20 %

 < 20 %

 < 20 %

Time Permitted to build up rated voltage at Rated RPM

 

< 5 sec provided engine reach the rated speed

Short Circuit Ratio

 

0.518

0.530

0.545

0.629

Short Circuit With Stand Time

sec

< 3 sec

Overload With Stand Capacity

%

10% overload for one hour once in 12 hours

For intermediate ratings, kindly contact nearest KOEL office

Notes
^ Tolerances Apply
*With 0.845 Specific Gravity of diesel ( 5 % Tolerance )

** Efficiency of Alternator as per standards IS 4722 and IEC 34-1
** For Site Conditions other than standard operating conditions consult KOEL for available prime power.

<< Back to Product List